Ex Breather Drain - (DP-E Series)


Redapt DP-E Series of Breather Drains provide a method of preventing moisture build-up within a hazardous area approved enclosure whilst ensuring the integrity and Ex approval of the installation is maintained.


Intended for use where an installation is subject to fluctuations in temperature which can lead to the formation of condensation and a subsequent moisture build-up.


The Breather Drain allows air within an enclosure to breathe with the surrounding atmosphere helping to prevent condensation and any potential damage to sensitive electric/electronic equipment housed within.


The Breather Drain will also maintain the IP66 rating of any enclosure to which it is installed.

The DP-E Series of stopping plugs are designed to be installed from the outside of an enclosure and can be used in a threaded or un-threaded entry hole. Ideally they should be located at the lowest point of an enclosure to ensure optimum draining of any moisture.

Redapt Breather Drains are designed for hazardous area applications and are certified to protection concept Exe “Increased Safety” for use in Zone 1 and Zone 2 applications.

Approved to the latest international standards, Breather Drains can be supplied with ATEX (CENELEC), IECEx, and GOST-R hazardous area certificates.

In addition CSA approval certificates can be supplied to cover use in North American and Canadian Class I Zone 1 Exe II applications.

DPE Breather Drain 2 imgs
Protection Method Exe – Increased Safety
Ingress Protection Maintained
IP66
Impact Resistance
20Nm (except aluminium and G.F. Nylon materials)
Ambient Temperature Range
-50°C to 85°C
Threadforms
ISO Metric, NPT, PG, NPS, BSPP, BSPT, ET.
Others on application
Materials
Brass CZ121, 316 Stainless Steel, Aluminium 6082,
Mild Steel EN1A and 30% Glass Filled Nylon
Plating
Nickel, Electroless Nickel, Zinc, others on application
O-Ring Materials
Nitrile, Silicone, Viton, EPDM, Neoprene,
others on application
Standards Approved To
IEC 60079-0, IEC 60079-7, IEC 61241-0, IEC 61241-1
ATEX Approval
SIRA99ATEX3050X  
IECEx Approval
IECEx SIR 08.0024U
GOST-R Approval
RU ?-GB.??06.?00106 – Russian
RU ?-GB.??06.?00106 – English
RU ?-GB.??06.?00106 Annex document – English
CSA Approval
1185887-2500003408 (LR 106084)

HOW TO ORDER WITH PART NUMBERS

Use the codes below to create part numbers for each product before contacting us to place an order. example: DP-E-1-1-04-S2
  TYPE CERTIFICATION MATERIAL PLATING THREAD O-RING
  Digit 1 & 2 Digit 3 Digit 4 Digit 5 Digits 6& 7 Digits 8 & 9
PRODUCT PART No. DP E ? ? ? ?
Material Codes
Digit 4

1 - Brass CZ121
3 - 316 stainless steel
4- Glass filled nylon


Plating Codes
Digit 5
0 - Unplated
1 - Electroless nickel
2 - Zinc

Thread Codes
Digits 6 & 7

04 - M20
05 - M25
06 - M32
29 - 1/2" NPT
30 - 3/4" NPT
31 - 1" NPT
Thread Length
Digits 8 & 9

S1 - 10mm with 2 holes
and Castelated L/Nut
S2 - 10mm with 2 holes
without Castelated L/Nut
S3 - 15mm with 3 holes
and Castelated L/Nut
S4- 15mm with 3 holes
without Castelated L/Nut